Energy Efficiency Measures
DISTRICT COOLING - CENTRAL PLANTS
District cooling systems distribute chilled water to multiple buildings.
Chilled water can be used for process cooling or heating and most commonly is
generated from a chilled water plant. Great amounts of discussion and debate
have gone into designing and optimizing chilled water systems. Overall, the goal
is always the same: to provide adequate cooling while minimizing the total
energy of the system which includes energy users such as chillers, cooling
towers, and pumps. The same principles can be applied when modifying an existing
system to improve energy efficiency. Opportunities can be broken into three
portions, generation, distribution, and end use. Keep in mind that a
modification to one of these three areas effects the others; they work together
as a system. The main goal should be to reduce overall energy costs.
Generation: Typically chilled water generation systems have three
components which should be optimized in coordination with each other. The key
parts are the chiller, the heat rejection system, and the pumping system(s).
Chiller efficiency is not a constant (nameplate) efficiency, but is dependent on
condensing temperatures, chilled water temperatures, and part load capacity.
Changing temperature setpoints, flowrates, and chiller staging all effect energy
efficiency. For heat rejection, Utah has a favorable climate for evaporative
cooling. By taking advantage of the low wet-bulb temperatures of our climate,
cooling towers can often provide cold enough water to cool a building or process
without the use of a chiller. This strategy is often referred to as “Free
Cooling,?and although it requires pumping and fan power, it avoids the energy
and demand expenses of compressor-based cooling. Adjusting approach temperatures
and reducing fan energy are examples of control strategies that minimize energy
required for heat rejection. Pumps are also a significant energy user in cooling
systems and should be included in energy efficiency plans. Variable speed
pumping is a common way to save pump energy and demand costs.
Distribution: Proper insulation minimizes losses. Minimizing pressure
drop and reducing pumping energy can have significant savings. Keys are to keep
the pipe diameter sufficiently large for the flow rates needed, minimize bends
(particularly right angled bends) and design layouts to minimize overall piping.
End-use: Maintaining heat transfer surfaces and valves reduces wasted
energy. Proper water treatment can minimize scaling which decreased heat
transfer efficiency. A leaking or stuck valve wastes chilled water, overcooling
a process or space that in turn must be heated to maintain the desired
temperature. Both cooling and heating energy are wasted. While proper
maintenance and operating strategies can minimize wasted energy, changes to
system control sequences or changes in the system configuration or equipment
need to be designed by a professional. A design engineer with experience with
district cooling systems can provide the best overall solution for an owner,
optimizing all of the components of the system.
For detailed technical information on designing a chilled water system for
optimum performance, the American Society of
Heating Refrigeration and Air-Conditioning Engineers (ASHRAE) is a great
resource.
Resources:
|